The WCT/ WDT cooling tower controllers represent the latest in technological and innovative advancements from Walchem. All of the standard features you’d expect from a conventional cooling tower controller are included, plus optional simple-to-use information management tools that enable water treatment professionals to deliver a more effective service to their customers. The WCT/ WDT controllers log sensor/ temperature values, water usage, relay and flow switch status and user settings. A USB memory stick is all that’s needed to extract the information. Download logs from the USB stick to a PC at your convenience, or copy your preferred treatment program settings to another controller to speed start-up. It couldn’t be easier!
WCT400/ 410 feed & bleed cooling tower controller
The WCT series cooling tower controllers control via conductivity measurement of high solids levels and adding low conductivity make-up water. Simultaneous control of chemical feed inhibits corrosion, solid precipitation and scale build up. Four chemical feed options are available
• feed & bleed, with or without feed lookout timer • feed after bleed has finished, as a percentage of time • feed as a
• percentage of time elapsed • feed as a percentage of make-up water
• built in data logger via USB flash stick for: event/ relay, reset logs and user configuration file import/ export
• plug and play USB technology
• choice of in-line or submersion sensor mounting
• standard wall mountable IP65 enclosure
• intermittent or continuously sampling
• water meter contact divider accumulates up to 100 pulses
• optional fully powered/ isolated 4-20mA output
• optional integrated flow switch manifold, which can be provided panel mounted
• universal power supply (100-265VAC)
• amplified & grounded ORP/ pH anti-foul flat surface electrodes with power supplied from controller, (more stable/ allows
• longer cable runs)
The WCT410 Series offers all of the WCT400 features as well as:
• programmable dual biocide timers: choice of 1, 7, 14, or 28-day cycles. Able to add a single biocide at any time, or dual alternating biocides, or dual independent biocides. Able to add a biocide up to 10 times a day • lockout timer • flow totaliser • conductivity based biocide pre-bleeds • powered alarm output relay
WDT400/ 410 feed & bleed cooling tower controller, with dual sensor control
The WDT series controllers feature dual input channels for use in control of cooling towers using two conductivity sensors (WDT400), or one conductivity and one ORP (or pH) sensor (WDT410). The WDT400 controller has the ability to control two cooling towers from the one unit.
In addition to the WCT400 specification the WDT400 offers:
• dual input channels for conductivity control of two towers
• output relays activate system bleed and chemical feed for each input channel
• choice of in-line or submersion sensor mounting
• independent flow switch and flow meter inputs are supported for each channel
• optional single, or dual fully powered/ isolated 4-20mA outputs
In addition to the WCT400 specification the WDT410 offers:
• dual input channels offers conductivity control of one tower, ORP/ pH control, (e.g. primary measured biocide) + two timed biocide adds
• in-line amplified & grounded ORP/ pH anti-foul flat surface electrodes with power supplied from controller
• programmable dual biocide timers: choice of 1, 7, 14, or 28-day cycles. Able to add a single biocide at any time, or dual alternating biocides, or dual independent biocides. Able to add a biocide up to 10 times a day
• alarm relay triggered by low conductivity, high conductivity, or no-flow conditions