Troubleshooting WCT/
WBL 300/400 series controllers
Serial number guide
Unit will not power up
No display
Pump or other device connected to relay will
not turn on
Controller fails conductivity
self-test
Controller registers contact from water meter
with no flow
Controller fails pH/ORP
self-test
Relay troubleshooting
Controller doesn't register flow from the
water meter
1.
Serial number guide:
For serial numbers prior to the end of
1999, there is a 6 digit format. The first two numbers
are the month (06 is June, 10 is October), the third
digit is the year (8 is 1998), and the last three digits
are sequential (308 is the three hundred and eighth
controller built in that month). Certain cooling tower
and boiler controllers begin with a letter V to indicate
that they were built with a new style enclosure. This is
important to know so that if we send a replacement front
panel it will fit correctly. Starting at the end of
1999, we went to a 10 digit format, such as 991109xxxx,
where the first two digits are the year, the next two
are the month, the next two are the day, and the last
four are sequential. (Top)
2.
Unit won't power up:
CAUSE: F1 fuse is
blown, due to a power surge or lightning
strike.Verify that
the fuse is blown by removing fuse and checking for
continuity from end to end using an ohmmeter. Replace F1
fuse, part number 102369. If the unit is still dead, and
the fuse is still intact then other components have been
damaged. The most common components to be damaged by a
power surge are MOV 1 and 2. If the problem occurs
repeatedly, install a surge suppressor on the power
source, or locate a cleaner source of power to use.
CAUSE: F1 fuse is blown,
due to a faulty component in the controller. Fuse
immediately blows when replaced.Remove all option boards and sensors. If
the fuse blows, the problem is within the controller, most
likely the front panel assembly. Try replacing it. If the
fuse survives, add option boards one at a time, restore
power, and see if the fuse still survives. The part which
when connected causes the fuse to blow is faulty, and
should be replaced. (Top)
3.
No display:
CAUSE: Improper
installation of the 4-20 mA option board. This cannot
happen at the factory, since the units are tested after
installation of an option board.If the option board is installed onto
its connector, but is off by one pin, the display will
not come up. Remove the option board and reinstall it
correctly.
CAUSE: Ribbon cable
installed backwards. This problem cannot happen at the
factory since the units are tested prior to
shipment.Install the
ribbon cable between the power supply board and the front
panel assembly correctly. Refer to the drawing in the
installation section of the instruction manual.
CAUSE: Installation
ambient temperature is higher than specified. This is
likely if the display seems to be completely
black.Install
controller where the ambient temperature will not exceed 70
degrees C (158 degrees F).
CAUSE: Defective solder
joint. Especially prevalent for controllers built before
1998.
If you can see a
poor connection between the display circuit board and the
processor board, and you are capable, you can try to touch
up the solder joint. If you are unable to fix it, order a
replacement front panel assembly (refer to the price list
for the appropriate part number). Keep in mind that any
attempts to do component-level repairs will void your
warranty.
CAUSE (for WBL
controllers only) Software bug. If the display is lit in
other menus but not in the top level menu, the problem is
caused by a bug in the software where the top level display
is not updated once a blowdown time limit error
occurs.
Reset the display by cycling the power off and back on
again. Troubleshoot the reason for the blowdown time limit
error to have occurred. (Top)
4.
Pump or other device connected to relay will not turn
on:
CAUSE: F2 fuse is
blown. Remove F2 fuse and measure from end to end with
an ohmmeter to verify fuse is blown. (Note: the WPH320,
WDP320 and WDP340 controllers do not have a F2 fuse,
since all outputs are either pulse or dry contact
relays.)
Replace the F2 fuse (part number 102432 if 115 V unit,
102370 if 230 V unit), and disconnect all devices from the
controller. If the fuse blows again, there is a problem
internal to the controller. If not, then connect one device
at a time to determine if the device is drawing too much
current and is causing the fuse to blow.
CAUSE: Faulty relay.
Verify that the relay is faulty by forcing the relay closed
(using the Manual Output feature for W300 series, or
adjusting the set point for W-130/230). Remove the terminal
block and measure across the pins using an ohmmeter. If the
meter does not indicate a connection, the relay is faulty.
Make sure that you compare the terminal block position as
pictured in the instruction manual with its actual
position. It is possible to place the terminal in the wrong
location, so that the relay that is closing is not
corresponding to the pins you are checking.
If you can do
component level troubleshooting, replace the part number
102329 relay. If not, replace the power supply board.
CAUSE: Faulty
connections. If you have checked the relay and know that it
is closing, and has power supplied to it (see above) then
the problem must be poor connections. With the terminal
block in place, force the relay closed and check for
continuity between the two terminals using an
ohmmeter.
If there is no connection, the terminal block is not making
a good connection with the pins. Make sure that you compare
the terminal block position as pictured in the instruction
manual with its actual position. It is possible to place
the terminal in the wrong location, so that the relay that
is closing is not corresponding to the pins you are
checking. Check all wiring connections. If the relay is
powered, make sure that both the Hot and Neutral wires are
secure. If using prewired pigtails, if you have voltage at
the terminal strip, but not at he end of the pigtail, then
the pigtail may have a broken wire or corroded connection.
Correct wiring connections.
CAUSE: Faulty power
supply board.
Replace power supply board. (Top)
5.
Controller fails conductivity
self-test:
CAUSE: Extended Cable.
The self test should read 1000 ± 20. If the cable
between the electrode and the controller has been
extended, expect the self test to decrease by 1 for each
foot (0.3 meter) of additional cable over the standard
10 feet (3 meters). If the cable is extended to 500
feet, then the limit of the calibration has been reached
(± 50% of the factory calibration value). Any coating on
the electrode can drop the conductivity further, causing
a calibration failure.
Move the electrode closer to the controller.
CAUSE: Faulty Electrode.
While the self test normally isolates the controller from
the electrode, there are ways for the electrode to fail
that will cause the self test to be too low. Disconnect the
electrode from the controller and repeat the self test. If
it now passes, the electrode is faulty.
Replace electrode.
CAUSE: Interference from
AC coupling on water meter cable. We have seen instances
where the water meter cable is routed through the same
conduit as AC voltage. If the water meter cable is
unshielded (and sometimes even if it is shielded) it can
pick up a voltage from the nearby AC wires. This can cause
false contacts, set points changing, or self test
failure. Disconnect the
water meter cable, and try the self test again. If the self
test now passes, route the water meter cable separated from
any wires carrying AC voltage.
CAUSE: Poor connection of
option board to processor board. If the problem is with
Sensor B of a dual input model, check the connection
between the option board and the processor board.
Remove power to the
controller. Remove the three screws that attach the option
board. If the board seems loose on the connector, the only
way to tighten it up is to put a small ball of solder on
each of the pins on the connector. The other option is to
replace the 190820 option board.
CAUSE: Faulty circuit
board. If the problem is with a single input controller, or
with Sensor A of a dual input controller, the processor
board is faulty. If the problem is with Sensor B of a dual
input model, the input option board is faulty. Component
level rework of these circuit boards is not
recommended.
Replace faulty circuit board. (Top)
6.
Controller registers contact from water meter with no
flow:
CAUSE: Interference
from AC coupling on water meter cable. We have seen
instances where the water meter cable is routed through
the same conduit as AC voltage. If the water meter cable
is unshielded (and sometimes even if it is shielded) it
can pick up a voltage from the nearby AC wires. This can
cause false contacts, set points changing, or self test
failure.
Disconnect the water meter cable from the controller (not
from the water meter), and see if the false contacts stop.
If they do stop, route the water meter cable separated from
any wires carrying AC voltage. (Top)
7.
Controller fails pH/ORP self-test:
CAUSE: Short on front
panel between circuit common and earth ground (the front
panel itself). If the bezel of the display is touching
the front panel, or legs of any components, then the
self test will fail. In older units, accumulations of
dust between the processor board or display and the
aluminum front panel can cause this problem.
Eliminate the cause of the short, or replace the front
panel assembly.
CAUSE: Failure of the
electrode. Leakage of water inside the pH/ORP housing can
cause the self test to be very low or fail. Inside the
electrode, a short between circuit common and earth ground
is developed. Verify this by repeating the self test with
the electrode wires disconnected from the controller. If
the self test now passes, then the electrode or its cable
is causing the problem.
Replace the pH/ORP electrode housing (not cartridge).
CAUSE: Interference from
AC coupling on water meter cable. We have seen instances
where the water meter cable is routed through the same
conduit as AC voltage. If the water meter cable is
unshielded (and sometimes even if it is shielded) it can
pick up a voltage from the nearby AC wires. This can cause
false contacts, set points changing, or self test failure.
Disconnect the
water meter cable, and try the self test again. If the self
test now passes, route the water meter cable separated from
any wires carrying AC voltage.
CAUSE: Poor connection of
option board to processor board. If the problem is with
Sensor B of a dual input model, check the connection
between the option board and the processor board.
Remove power to the controller. Remove the three screws
that attach the option board. If the board seems loose on
the connector, the only way to tighten it up is to put a
small ball of solder on each of the pins on the connector.
The other option is to replace the option board.
CAUSE: Faulty circuit
board. If the problem is with a single input controller, or
with Sensor A of a dual input controller, the processor
board is faulty. If the problem is with Sensor B of a dual
input model, the input option board is faulty. Component
level rework of these circuit boards is not
recommended.
Replace faulty circuit board. (Top)
7.
Relay troubleshooting:
Start at the device (pump, valve, etc.)
and work back towards the relay. With the output in
question activated:
1. Manually cycle the output on and off. If you not hear
the relay click open and closed (assuming you are in a
quiet location!) skip to 9 below, otherwise:
2. Check F2 fuse (if present; not needed
for WPH320, WDP320 or WDP340 controllers) by measuring
voltage between Neutral and both ends of the fuse. If
voltage is present at the bottom of the fuse, but not
present at the top of the fuse, it is blown and needs to be
replaced. Look for any obviously burned circuits or
components. If a fuse continuously blows, then a
device attached is drawing too much amperage. Note that
motors draw 3-4 times more current at startup than the
rated current. The limit for motors is 1/8 HP.
3. Check for voltage at the device. If
present, the device is defective. If not present:
4. Check for voltage at the terminal strip
(between Neutral terminal and the NO terminal of the active
output). If present, the wiring between the terminal strip
and the device is defective. If not present:
5. Check that the terminal strip is
installed in the correct location as compared to the
instruction manual. If correct:
6. Check to see if the Neutral wire of the
device is connected correctly. If correct:
7. Check to see if the relay is internally
powered or dry contact. A powered relay will be labeled NO
(or both NO and NC for the one furthest to the right) while
a dry contact will be NO and COM. If it is a dry contact,
verify that voltage is supplied to the COM terminal. If OK:
8. Remove the terminal block and check for
voltage between Neutral and the pin that the terminal block
connects to. If present, the terminal block connection is
poor or the terminal block is defective. If not present:
9. Measure DC voltage on IC U2 between pin
8 (ground) and pin 1 (for K1 relay), or pin 2 (for K2
relay) …or pin 5 (for K5 relay). The IC may be
partially hidden by the 4-20 mA option board. Remove the
option board before taking measurements. You should see 5
VDC when the output is active, and 0 VDC when output is
off. If not, the ribbon cable is probably defective. If OK:
10. Measure DC voltage on IC U2 between
pin 8 and pin 16 (for K1 relay) or pin 15 (for K2 relay)
… or pin 12 (for K5 relay). This should be 0.7 VDC
when the output is active, and 9 VDC when output is off. If
not, then the IC U2 is defective. If OK:
11. Relay is defective.
(Top)
8.
Controller does not register flow from the water
meter:
CAUSE: The controller
input if faulty. Test this by removing the water meter
cable from the controller terminal strip and repeatedly
shorting the input and removing the short. If the
controller does not register the contacts, it is faulty.
Replace the
label/panel assembly.
CAUSE: The water meter
cable is faulty. If the controller input tests OK, then
connect the water meter cable and try to short the opposite
end of the cable. If the controller registers flow, the
cable if OK.
Replace the cable.
CAUSE: There is no water
flow.
Look for closed valves, verify that there is flow through
the makeup line. Restore flow.
CAUSE: Water meter is
faulty.
Replace water meter. (Top)
Copyright © 2009 Walchem. All rights reserved.
